| Microgrid Name | Generation Bus | Minimum 1 hr Load (kW) | Average 1 hr Load (kW) | Average Daytime 1 hr Load (kW) | Maximum 1 hr Load (kW) | Maximum 1 hr Critical Load (kW) | Existing Fossil Generation (kW) | New Fossil Generation (kW) | Existing Solar (kW) | New Solar (kW) | Existing Battery Power (kW) | Existing Battery Energy Storage (kWh) | New Battery Power (kW) | New Battery Energy Storage (kWh) | Existing Wind (kW) | New Wind (kW) | Total Generation on Microgrid (kW) | Renewable Generation (% of Annual kWh) | Emissions (Yr 1 Tons CO2) | Emissions Reduction (Yr 1 % CO2) | Average Outage Survived (h) | O+M Costs (Yr 1 $ before tax) | CapEx ($) | CapEx after Tax Incentives ($) | Net Present Value ($) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mg0 | 633 | 60 | 178 | 247 | 306 | 400 | 0 | 200 | 440 | 335 | 0 | 0 | 144 | 816 | 0 | 1 | 1,120 | 58 | 449 | 34 | 200 | 17,589 | 1,456,124 | 1,102,058 | -612,341 |
| mg1 | 645 | 25 | 139 | 215 | 385 | 170 | 0 | 44 | 0 | 575 | 0 | 0 | 112 | 286 | 0 | 1 | 732 | 51 | 405 | 50 | 871 | 10,369 | 1,434,038 | 967,481 | -90,709 |
| mg2 | 670 | 639 | 1,176 | 1,449 | 2,034 | 1,810 | 265 | 640 | 0 | 5,032 | 0 | 0 | 828 | 5,226 | 0 | 1 | 6,767 | 54 | 3,213 | 53 | 241 | 103,951 | 11,920,186 | 7,609,454 | -720,151 |
| mg3 | 675c_residential1 | 60 | 178 | 247 | 306 | 485 | 0 | 201 | 440 | 335 | 0 | 0 | 144 | 807 | 0 | 0 | 1,120 | 58 | 451 | 34 | 201 | 17,574 | 1,461,963 | 1,110,885 | -624,337 |
| Summary | None | 789 | 1,492 | 2,158 | 2,713 | 2,865 | 265 | 1,085 | 880 | 6,277 | 0 | 0 | 1,228 | 7,135 | 0 | 3 | 9,739 | 55 | 4,518 | 50 | 200 | 149,483 | 16,272,311 | 10,789,878 | -2,047,538 |
2022-07-18 14:26:12.153356
{'MODEL_DIR': 'auto3mg', 'BASE_DSS': 'lehigh_base_3mg.dss', 'LOAD_CSV': 'lehigh_load.csv', 'QSTS_STEPS': 480, 'FOSSIL_BACKUP_PERCENT': 0.5, 'REOPT_INPUTS': {'solar': 'on', 'wind': 'off', 'battery': 'on', 'year': '2017', 'analysisYears': '25', 'discountRate': '0.083', 'energyCost': '0.12', 'demandCost': '20', 'urdbLabelSwitch': 'off', 'wholesaleCost': '0', 'solarCost': '1600', 'windCost': '4989', 'batteryPowerCost': '840', 'batteryCapacityCost': '420', 'batteryPowerCostReplace': '410', 'batteryCapacityCostReplace': '200', 'batteryPowerReplaceYear': '10', 'batteryCapacityReplaceYear': '10', 'dieselGenCost': '1000', 'solarMin': 0, 'windMin': 0, 'batteryPowerMin': 0, 'batteryCapacityMin': 0, 'solarMax': '100000', 'windMax': '100000', 'batteryPowerMax': '100000', 'batteryCapacityMax': '100000', 'dieselMax': '100000', 'solarExisting': 0, 'criticalLoadFactor': '1', 'outageDuration': '48', 'fuelAvailable': '10000', 'genExisting': 0, 'minGenLoading': '0.3', 'batteryKwExisting': 0, 'batteryKwhExisting': 0, 'windExisting': 0, 'dieselFuelCostGal': 3, 'dieselCO2Factor': 22.4, 'dieselOMCostKw': 25, 'dieselOMCostKwh': 0.02, 'value_of_lost_load': '100', 'solarCanCurtail': True, 'solarCanExport': True, 'dieselOnlyRunsDuringOutage': True}, 'MICROGRIDS': {'mg0': {'loads': ['634a_data_center', '634b_radar', '634c_atc_tower'], 'switch': ['632633'], 'gen_bus': '633', 'gen_obs_existing': ['solar_634_existing'], 'critical_load_kws': [160.0, 120.0, 120.0], 'max_potential': '700', 'max_potential_diesel': '1000000', 'battery_capacity': '10000'}, 'mg1': {'loads': ['645_hangar', '646_office'], 'switch': ['632645'], 'gen_bus': '645', 'gen_obs_existing': [], 'critical_load_kws': [170.0, 0.0], 'max_potential': '700', 'max_potential_diesel': '1000000', 'battery_capacity': '10000'}, 'mg2': {'loads': ['684_command_center', '692_warehouse2', '675a_hospital', '675b_residential1', '675c_residential1', '611_runway', '652_residential', '670a_residential2', '670b_residential2', '670c_residential2'], 'switch': ['632670'], 'gen_bus': '670', 'gen_obs_existing': ['fossil_675_existing'], 'critical_load_kws': [1155.0, 0.0, 485.0, 0.0, 0.0, 170.0, 0.0, 0.0, 0.0, 0.0], 'max_potential': '700', 'max_potential_diesel': '1000000', 'battery_capacity': '10000'}}, 'FAULTED_LINE': '670671', 'DIESEL_SAFETY_FACTOR': False, 'OUTAGE_CSV': 'lehigh_random_outages.csv'}
The critical loads specified for microgrid mg0 are larger than the max kw of the total loadshape. Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system. Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.
| Microgrid | Location | Recommended Upgrade | Cost Estimate ($) |
|---|---|---|---|
| mg0 | mg0 | Microgrid Design | 100,000 |
| mg0 | mg0 | Microgrid Controls | 100,000 |
| mg0 | ['632633'] | SCADA disconnect switch | 50,000 |
| mg0 | 634a_data_center | AMI disconnect meter | 500 |
| mg0 | 634b_radar | AMI disconnect meter | 500 |
| mg0 | 634c_atc_tower | AMI disconnect meter | 500 |
| mg1 | mg1 | Microgrid Design | 100,000 |
| mg1 | mg1 | Microgrid Controls | 100,000 |
| mg1 | ['632645'] | SCADA disconnect switch | 50,000 |
| mg1 | 645_hangar | AMI disconnect meter | 500 |
| mg1 | 646_office | AMI disconnect meter | 500 |
| mg2 | mg2 | Microgrid Design | 100,000 |
| mg2 | mg2 | Microgrid Controls | 100,000 |
| mg2 | ['632670'] | SCADA disconnect switch | 50,000 |
| mg2 | 684_command_center | AMI disconnect meter | 500 |
| mg2 | 692_warehouse2 | 3-phase relay | 20,000 |
| mg2 | 675a_hospital | 3-phase relay | 20,000 |
| mg2 | 675b_residential1 | 3-phase relay | 20,000 |
| mg2 | 675c_residential1 | 3-phase relay | 20,000 |
| mg2 | 611_runway | AMI disconnect meter | 500 |
| mg2 | 652_residential | AMI disconnect meter | 500 |
| mg2 | 670a_residential2 | AMI disconnect meter | 500 |
| mg2 | 670b_residential2 | AMI disconnect meter | 500 |
| mg2 | 670c_residential2 | AMI disconnect meter | 500 |
| mg3 | mg3 | Microgrid Design | 100,000 |
| mg3 | mg3 | Microgrid Controls | 100,000 |
| mg3 | ['692675'] | SCADA disconnect switch | 50,000 |
| mg3 | 675a_hospital | AMI disconnect meter | 5,000 |
| mg3 | 675b_residential1 | AMI disconnect meter | 5,000 |
| mg3 | 675c_residential1 | AMI disconnect meter | 5,000 |